Mountingandwiring
Wiresizewidth 0.5...2.5mm
2
AWG20..AWG14
Wirestrippinglength 8...9mm 0.33inch
LED
Ifthepowersupplyunitisconnectedcorrectlyandthepowersupplyisswitchedon,thetwoupperLEDsin
theterminalprismaregreen.TheleftLED(Us)indicatestheCPUsupply.TherightLED(Up)indicatesthe
terminalsupply.TheotherLEDsindicatetheTerminalBusstatus.AdetaileddescriptionoftheLEDscanbe
foundinsection“LEDtroubleshooting”.
PEpowercontacts
Attention
Powerkontakt"PE"
The“PE”powercontactmustnotbeusedforotherpotentials."PE"und"0V"(24VCXSys
temsupply)havetobeonthesamepotential.(connectedinthecabinet)DerPowerkontakt
"PE"darfnichtfüranderePotentialeverwendetwerden."PE"und"0V"(24VSystemver
sorgung)müssenaufdemgleichenPotentialliegen.(imSchaltschrankverbunden)The
wiringthecabinethastofollowtheNormENEN602041:2006:SafetyofmachineryElec
tricalequipmentofmachines(PELV=ProtectiveExtraLowVoltage)EN602041:2006
chapter6.4.1:b):Onesideofthecircuitorapointoftheenergysourceofthecircuitmust
beconnectedtoprotectiveearthsystem
Attention
Interruptpowersupply/switchingoff
Ifthepowersupplyshouldbedisconnectedthe"0V"mustnotbedisconnected.Alwaysdis
connectthe“24V”wirefirst.Otherwisetherecanbeelectricalcurrentflowviatheshield.
Possiblyconnecteddeviceswithownpowersupply(e.g.panel)musthavethesameelec
tricalpotentialfor"PE"and"GND"astheCXunit.OtherwisetheCXunitand/orthecon
necteddevicecanbedamaged.