Mountingandwiring
2. Thewirecannowbeinsertedintotheroundterminalopeningwithoutanyforce.
3. Theterminalclosesautomaticallywhenthepressureisreleased,holdingthewiresafelyand
permanently.
Wirecrosssection 0,5...2.5mm
2
AWG20..AWG14
Striplength 8...9mm 0.33inch
LED
Ifthepowersupplyunitisconnectedcorrectlyandthepowersupplyisswitchedon,thetwoupperLEDsin
theterminalprismaregreen.TheleftLED(Us)indicatestheCPUsupply.TherightLED(Up)indicatesthe
terminalsupply.TheotherLEDsindicatetheTerminalBusstatus.AdetaileddescriptionoftheLEDscanbe
foundinsection“LEDtroubleshooting”.
PEpowercontacts
Attention
Powercontact“PE”
The“PE”powercontactmustnotbeusedforotherpotentials.“PE”and“0V”(24Vsystem
supply)mustbeatthesamepotential(connectedinthecontrolcabinet).Thecablinginthe
controlcabinetmustbedoneinaccordancewiththestandardEN602041:2006PELV=
ProtectiveExtraLowVoltage.EN602041:2006section6.4.1:b:onesideofthecircuitor
onepointoftheenergysourceofthiscircuitmustbeconnectedtotheprotectiveconductor
system.
Attention
Interruptionofthepowersupply/switchingoff
Thedevicemaynotbeswitchedoffbydisconnectingtheground.The24Vlinemustal
waysbedisconnected,asotherwisecurrentmaycontinuetoflowviathescreendepending
onthedevice.Anyconnecteddeviceswiththeirownpowersupply(e.g.apanel)musthave
thesamepotentialfor“PE”and“GND”astheCXsystem(nopotentialdifference).Other
wisedamagecanoccurbothtothecontrollerandtotheperiphery.